Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

02/04/2009

Applicant:

DND NEFFSON CO

Description:

Full Fire Prevention Inspection. Myra Garcia 690-1250

Outstanding Inspections

Case Number: T09FR00512
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
02/04/2009 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. _____1. Remove the storage from obstructing the automatic sprinkler heads located above the manager office in the back room.
02/04/2009 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. _____1. Replace the missing ceiling tile located in the back room. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
02/04/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1. Repair or replace the the broken emergency lighting unit located in the men's Jeans area. _____2. The EXIT sign located by the hats shall have emergency back-up power. _____3. The EXIT sign located above the North exit door shall have emergency back-up power.
02/04/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. _____1. Remove the storage located in the North EXIT access corridor.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00512
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/18/2009 INSP - FULL JBURGE Approved All noted Tucson Fire Code violation have been corrected.