Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

02/03/2009

Applicant:

DND NEFFSON CO

Description:

Full Fire Prevetion Inspection.

Outstanding Inspections

Case Number: T09FR00488
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
02/03/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3- Remove all storage from obstructing the electrical service equipment located in the back room.
02/03/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5- Repair or replace the broken emergency lighting unit located iin the mall exit corridor.
02/03/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.4- The rear exit door shall not be disguised to look like the wall.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00488
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/24/2009 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.