Case: T09FR00419
Case Details
Entered Date:
01/30/2009
Applicant:
COPE BEHAVIORAL SERVICES INC
Description:
requesting fire inspection. contact Maura Cassidy 884-0707 x 670. (3 yr cycle)
Outstanding Inspections
Case Number: T09FR00419
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/04/2009 | VIOL - PRECAUTION AGAINST FIRE | JLOYA | Violation | TFC 315.2.1 - Ceiling clearance. Storage shall be maintained 2 feet or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings. |
| 02/04/2009 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 903.3.3 Obstructed locations. Automatic sprinklers shall be installed with due regard to obstructions that will delay activation or obstruct the water distribution pattern. Automatic sprinklers shall be installed in or under covered kiosks, displays, booths, concession stands, or equipment that exceeds 4 feet (1219 mm) in width. Not less than a 3-foot (914 mm) clearance shall be maintained between automatic sprinklers and the top of piles of combustible fibers. _ Sidewall sprinklers obstructed. (Veronica's office) _ Basement closet lacks sprinkler coverage. |
| 02/04/2009 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | TFC 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____ All sprinkler heads and escutcheons shall be cleaned, replaced, or adjusted to meet the requirements of this code. ____Remove masking tape from sprinklers. |
| 02/04/2009 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | TFC 906.7 - Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR00419
Case Description: INSPECTION
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/04/2009 | INSP - FULL | JLOYA | Approved | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext.146. |
| 03/16/2009 | INSP - REINSPECTION | JLOYA | Approved | All violations abated |