Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T09FR00261
Case Details
Entered Date:
01/20/2009
Applicant:
BUILDER S FASHION SQUARE LLC
Description:
SPRINKLER INSPECTION
Outstanding Inspections
Case Number: T09FR00261
Case Status: FIELD
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected | ||
01/20/2009 | INSP - NIGHT | EDESCHAI | Correction Required | DURING THE ANNHUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS 1) SIGNAGE SHALL BE REMOVED FROM SPRINKLER PIPING 2) OUTSIDE OF ENTRY TO NURSERY TWO UPRIGHT SPRINKLERS ARE POSSIBLY PAINTED 3) SOUTH END OF WORKOUT AREA, THERE ARE 3 UPRIGHT PAINTED SPRINKLER HEADS. THEY SHALL BE CHANGED OUT 4) ABOVE ENTRY TO STUDIO B, THERE ARE PAINTED UPRIGHT SPRINKLER HEADS, THEY SHALL BE CHANGED OUT 5) WEST OF STUDIO B THERE ARE 2 PAINTED UPRIGHT HEADS AND 1 PAINTED PENDANT HEAD. THEY SHALL BE CHANGED OUT 6) ABOVE TRICEPS EXTENTION MACHINE, BY STUDIO B, THERE IS A PAINTED UPRIGHT SPRINKLER HEAD. IT SHALL BE CHANGED OUT 6) BY TREADMILL MACHINES, THERE ARE SEVERAL PAINTED UPRIGHT SPRINKLER HEADS. THEY SHALL BE CHANGED OUT 7) ABOVE EGGCRATE CEILING IN LOCKER ROOM, ALL SPRINKLER HEADS THAT ARE CORRODED OR PAINTED SHALL BE CHANGED OUT 8) NURSERY, 2 SPRINKLERS ARE TO CLOSE TOGEATHER, ONE MAY BE PLUGGED OUT 9) NURSERY, STUDIO B, STUDIO A, THE INSULATION THAT IS BLOCKING SPRINKLER SPRAY PATTERNS SHALL BE RELOCATED 10) THE STOREROOM BY THE FRONT ENTRY SHALL HAVE SPRINKLER PROTECTION ADDED 11) NURSER OFFICE, SPRINKLER PROTECTION SHALL BE ADDED TO THIS AREA 12) SPRINKLER PROTECTION SHALL BE ADDED TO THE SHORT HALL BY THE OLD TANNING ROOMS 13) LARGE JANITOR ROOM, ADD SPRINKLER PROTECTION TO THE STORAGE CLOSET 14) LARGE JANITORS ROOM, SPRINKLERS ARE TO CLOSE TOGEATHER AND TO FAR OFF A WALL, RELOCATE TO CORRECT 15) SPINNING ROOM, CHANGE OUT THE SPRINKLER WITH THE BENT DEFLECTORR 16) SPRINKLERS IN THE SPINNING ROOM SHALL ALL BE OF THE SAME TEMPERATURE RATING 17) EAST WALL ABOVE CHANGE YOUR BODY CHANGE YOUR LIFE SIGN, THERE ARE 6 UPRIGHT SPRINKLERS INSTALLED IN THE PENDANT POSITION. THE CORRECT SPRINKLERS SHALL BE INSTALLED 5) |