Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

01/14/2009

Applicant:

TUCSON SIXTH AVENUE RENTALS LLC

Description:

Long jhon silver full fire inspection.

Outstanding Inspections

Case Number: T09FR00231
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
01/14/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring.
01/14/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.5.1 System test. Systems shall be inspected and tested for proper operation at 6-month intervals. Tests shall include a check of the detection system, alarms and releasing devices, including manual stations and other associated equipment.
01/14/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation TFC 906.7 - Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions.
01/14/2009 VIOL - MEANS OF EGRESS JLOYA Violation TFC 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit signs

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00231
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
01/14/2009 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext.146
01/29/2009 INSP - REINSPECTION JLOYA Approved All violations abated.