Applicant:

PHE-SON PROPERTIES

Description:

Whataburger full fire inspection.

Outstanding Inspections

Case Number: T09FR00229
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
01/14/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. __ Provide protection for the cord operating drive thru window at point of entrance.
01/14/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.11.6.3 - Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises.
01/14/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation TFC 906.6 - Unobstructed and unobscured. Portable fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers.
01/14/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00229
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
01/14/2009 INSP - FULL JLOYA Approved Correct the following fire code violations found 1-14-09. Thank you for your cooperation.
01/29/2009 INSP - REINSPECTION JLOYA Approved All violations abated.