Case: T09FR00227
Case Details
Entered Date:
01/14/2009
Applicant:
DND NEFFSON CO
Description:
Full Fire Prevention Inspection. Krystle Zelk 408-7958
Outstanding Inspections
Case Number: T09FR00227
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/14/2009 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. _____1. Remove all storage from obstructing the sprinkler heads located in the back room. |
01/14/2009 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. _____1.Remove all storage from obstructing the electrical service equipment located in the back room. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
01/14/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1. The emergency lighting unit on the EXIT sign in the back room shall be repaired. _____2. Repair or replace the broken emergency lighting unit located in "Dudes 2". |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR00227
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/17/2009 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violation have been corrected. |