Description:

CT Nails full fire inspection.

Outstanding Inspections

Case Number: T09FR00097
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
01/09/2009 INSP - FULL JLOYA Violation Correct the following fire code violations found 1-8-09. Thank you for your cooperation.
01/09/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.
01/09/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00097
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
01/26/2009 INSP - REINSPECTION JLOYA Approved All violations abated.