Case: T09FR00072
Case Details
Entered Date:
01/08/2009
Applicant:
SAN XAVIER PLAZA LLC
Description:
Malenas beauty salon full fire inspection.
Outstanding Inspections
Case Number: T09FR00072
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/08/2009 | INSP - FULL | JLOYA | Violation | Correct the following fire code violations found 1-7-09. Thank you for your cooperation. |
01/08/2009 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Replace with approved power strip. _____ Remove extension cord and/or replace with approved permanent electrical power source. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR00072
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/21/2009 | INSP - REINSPECTION | JLOYA | Approved | All violations abated. |