Case: T09FR00069
Case Details
Entered Date:
01/08/2009
Applicant:
SAN XAVIER PLAZA LLC
Description:
Tortilla factory full fire inspection.
Outstanding Inspections
Case Number: T09FR00069
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/08/2009 | INSP - FULL | JLOYA | Violation | Correct the folowing fire code violations found 1-7-09. Thank you for your cooperation. |
01/08/2009 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels |
01/08/2009 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Replace with approved power strip. _____ Remove extension cord and/or replace with approved permanent electrical power source. |
01/08/2009 | VIOL - FIRE RESIST.RATED CONST | JLOYA | Violation | TFC 703.1 - The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. ***Replace missing ceiling tiles. |
01/08/2009 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | TFC 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____ All sprinkler heads and escutcheons shall be cleaned, replaced, or adjusted to meet the requirements of this code. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR00069
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/21/2009 | INSP - REINSPECTION | JLOYA | Approved | All violations abated. |