Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

01/07/2009

Applicant:

DEVELOPMENT TRADING AND TRANSACTING

Description:

FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T09FR00054
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
01/07/2009 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Violation 2006 IFC 605.1 NEED OUTLET PLATE COVER BY MICROWAVE #2 NEED OUTLET PLATE COVER BY SINK CUTTING BOARD NEED OUTLET PLATE BEHIND FREZZER
01/07/2009 VIOL - FIRE RESIST.RATED CONST MWAINWRI Violation 2006 IFC 703.1 REPLACE CEILLING TILES IN STORAGE CLOSET NEXT TO OFFICE
01/07/2009 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Violation 2006 IFC 904.11.6.1 REPLACE THE 2 WORN OUT HOOD FILTERS
01/07/2009 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Violation 2006 IFC 904.11.6.3 CLEAN FILTERS AND HOOD SYSTEM TO THE ROOF
01/07/2009 VIOL - MEANS OF EGRESS MWAINWRI Violation 2006 IFC 1008.1.8 REPLACE DBL KEYED LOCK ON REAR KITCHEN DOOR WITH A THUMB TURN LOCK

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00054
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/09/2009 INSP - FULL MWAINWRI Approved