Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

01/06/2009

Applicant:

PARK VIEW PLAZA INC

Description:

LIttle caesars full fire inspection

Outstanding Inspections

Case Number: T09FR00027
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
01/06/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels.
01/06/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Replace with approved power strip. _____ Remove extension cord and/or replace with approved permanent electrical power source.
01/06/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
01/06/2009 VIOL - FIRE RESIST.RATED CONST JLOYA Violation TFC 703.1 - The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. ***Replace missing ceiling tiles.
01/06/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.11.6.3 - Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises.
01/06/2009 VIOL - COMPRESSED GASES JLOYA Violation Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be by one of the following methods: 1. Securing containers, cylinders and tanks to a fixed object with one or more restraints.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00027
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
01/06/2009 INSP - FULL JLOYA Approved Correct the following fire code violations found 1-5-09. Thank you for your cooperation.
01/27/2009 INSP - REINSPECTION JLOYA Approved All violations abated.