Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

01/06/2009

Applicant:

ZETA PARTNERSHIP

Description:

FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T09FR00026
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
01/06/2009 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Violation 2006 IFC 605.1 WIRE WARMER WITH A OUTLET AND PROPER PLUG
01/06/2009 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Violation 2006 IFC 605.5 REMOVE EXTENSION CORD THROUGH CEILING AND HARD WIRE THE REFRIGERATOR
01/06/2009 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Violation 2006 IFC 904.11.6.3 CLEAN THE FILTERS
01/06/2009 VIOL - MEANS OF EGRESS MWAINWRI Violation 2006 IFC 1008.1.8.4 REMOVE THE SLIDE BOLT ON THE REAR EXIT DOOR
01/06/2009 VIOL - MEANS OF EGRESS MWAINWRI Violation 2006 IFC 1027.3 REPAIR EXIT SIGN BY BATHROOMS

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00026
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/18/2009 INSP - FULL MWAINWRI Approved