Case: T09FR00015
Case Details
Entered Date:
01/05/2009
Applicant:
PARK VIEW PLAZA INC
Description:
Superior cleaners full fire inspection.
Outstanding Inspections
Case Number: T09FR00015
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/05/2009 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels |
01/05/2009 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Replace with approved power strip. _____ Remove extension cord and/or replace with approved permanent electrical power source. |
01/05/2009 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. |
01/05/2009 | VIOL - FIRE RESIST.RATED CONST | JLOYA | Violation | TFC 703.1 - The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. ***Replace missing ceiling tiles. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR00015
Case Description: INSPECTION
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/05/2009 | INSP - FULL | JLOYA | Approved | Correct the following fire code violations found 1-5-09. Thank you for your cooperation. |
01/20/2009 | INSP - REINSPECTION | JLOYA | Approved | All violations abated. |