Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

01/05/2009

Applicant:

PARK VIEW PLAZA INC

Description:

Rodolfo's taco shop full fire inspection.

Outstanding Inspections

Case Number: T09FR00013
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
01/05/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Replace with approved power strip. _____ Remove extension cord and/or replace with approved permanent electrical power source.
01/05/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.11.5 Commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. ***A K class extinguisher shall be installed according to this code.
01/05/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.11.6.3 - Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises.
01/05/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation TFC 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____ All sprinkler heads and escutcheons shall be cleaned, replaced, or adjusted to meet the requirements of this code.
01/05/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted __ Remove slide bolt from front door.
01/05/2009 VIOL - COMPRESSED GASES JLOYA Violation Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be by one of the following methods: 1. Securing containers, cylinders and tanks to a fixed object with one or more restraints.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00013
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
01/05/2009 INSP - FULL JLOYA Approved Correct the following fire code violations found 1-5-09. Thank you for your cooperation.
01/21/2009 INSP - REINSPECTION JLOYA Approved all violations abated.