Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

12/19/2008

Applicant:

FOOTHILLS BUSINESS VENTURES LLC 90% &

Description:

La Princesa jewlery full fire inspection.

Outstanding Inspections

Case Number: T08FR04768
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
12/19/2008 VIOL - ADMINISTRATION JLOYA Violation 105.6.11 Cutting and welding. An operational permit is required to conduct cutting or welding operations within the jurisdiction.
12/19/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels.
12/19/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Replace with approved power strip. _____ Remove extension cord and/or replace with approved permanent electrical power source
12/19/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
12/19/2008 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities.
12/19/2008 VIOL - COMPRESSED GASES JLOYA Violation 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be by one of the following methods: 1. Securing containers, cylinders and tanks to a fixed object with one or more restraints.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04768
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
12/19/2008 INSP - FULL JLOYA Approved Correct the following fire code violation found 12-18-08. For your cooperation, thank you.
01/20/2009 INSP - REINSPECTION JLOYA Approved all violations abated