Description:

FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T08FR04740
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
12/16/2008 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Violation 2006 IFC 605.5 REMOVE EXTENSION CORD ON REFRIGERATOR IN BREAK RM
12/16/2008 VIOL - FIRE RESIST.RATED CONST MWAINWRI Violation 2006 IFC 703.1 REPLACE MISSING DRYWALL IN CEILILNG IN AC ROOM REPLACE MISSING DRYWALL IN BEAVERAGE OVERSTOCK RM REPLACE MISSING CEILING TILES IN LIQUOR LOCK UP ROOM
12/16/2008 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Violation 2006 IFC 901.6 SERVICE AND TAG ALL FIRE EXTINGUISHERS SERVICE AND TAGE SPRINKLER SYSTEM

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04740
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/04/2009 INSP - FULL MWAINWRI Approved