Case: T08FR04739
Case Details
Entered Date:
12/16/2008
Applicant:
MARBLE JOHN A
Description:
FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T08FR04739
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/16/2008 | VIOL - BUILDING SVCS & SYSTEMS | MWAINWRI | Violation | 2006 IFC 605.1 REPLACE MISSING PLATE ON RECEP ON NORTH SIDE OF SHOWROOM REPLACE MISSING SWITCH PLATE IN SHOWROOM NEED BLANK COVER PLATE BY ELEC PANEL B |
| 12/16/2008 | VIOL - FIRE PROTECTION SYSTEMS | MWAINWRI | Violation | 2006 IFC 901.6 SERVICE AND TAG ALL FIRE EXTINGUISHERS |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04739
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/07/2009 | INSP - FULL | MWAINWRI | Approved |