Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

12/15/2008

Applicant:

CORNIDEZ ARMANDO P & LAURA I CP/RS

Description:

Joyeria Cornidez full fire inspection.

Outstanding Inspections

Case Number: T08FR04735
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
12/15/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels.
12/15/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes
12/15/2008 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities.
12/15/2008 VIOL - WELDING & OTHER HOT WRK JLOYA Violation 2603.3 Hot work program permit. Hot work permits, issued by an approved responsible person under a hot work program, shall be available for review by the fire code official at the time the work is conducted and for 48 hours afterwork is complete. __Welding area is to be cleared of all combustible, Gas tanks to be downsized.
12/15/2008 VIOL - COMPRESSED GASES JLOYA Violation 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be by one of the following methods: 1. Securing containers, cylinders and tanks to a fixed object with one or more restraints.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04735
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
12/15/2008 INSP - FULL JLOYA Approved Correct the following fire code violations found 12-15-08.
01/12/2009 INSP - REINSPECTION JLOYA Approved All violations abated.