Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T08FR04724
Case Details
Entered Date:
12/12/2008
Applicant:
GEE JANE TR
Description:
Ana's party decorations full fire inspection.
Outstanding Inspections
Case Number: T08FR04724
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/12/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | Blocked electrical panel: TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer. |
12/12/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Replace with approved power strip. _____ Remove extension cord and/or replace with approved permanent electrical power source. |
12/12/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes |
12/12/2008 | VIOL - COMPRESSED GASES | JLOYA | Violation | 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be by one of the following methods: 1. Securing containers, cylinders and tanks to a fixed object with one or more restraints. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04724
Case Description: INSPECTION
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/12/2008 | INSP - FULL | JLOYA | Approved | Correct the following fire code violations found 12-11-08. |
01/26/2009 | INSP - REINSPECTION | JLOYA | Approved | All violations abated. |