Case: T08FR04714
Case Details
Entered Date:
12/11/2008
Applicant:
ROSE DELA DMA FLP
Description:
La bodega warehouse full fire inspection.
Outstanding Inspections
Case Number: T08FR04714
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/11/2008 | VIOL - PRECAUTION AGAINST FIRE | JLOYA | Violation | TFC 315.2.1 - Ceiling clearance. Storage shall be maintained 2 feet or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings. |
12/11/2008 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch high on a contrasting background, |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04714
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/11/2008 | INSP - FULL | JLOYA | Approved | Correct the following code violations founs during fire/safety inspection conducted 12/11/08. |