Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

12/11/2008

Applicant:

SANDELMAN SUSAN TR

Description:

Full Fire Prevention Inspection Building Rep: Jeff Kubinski Phone # 520-408-2103

Outstanding Inspections

Case Number: T08FR04703
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
12/11/2008 INSP - FULL JLONGO Correction Required Full Fire Prevention Inspection completed. Please correct the following Tucson Fire Code Violations.
12/11/2008 VIOL - BUILDING SVCS & SYSTEMS JLONGO Correction Required 605.4 Multi-plug adapters Multi-plug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC electrical code shall be prohibited. _____ All Multi-plug adapters shall be removed and/or replace with approved fused power strips. (OFFICE #1) 605.5 Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring. Cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ All extension cords shall be removed and/or replace with approved fused power strips. (Office 1 & 2, couches) 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be allowed. _____ Properly secure the loose hanging wires located in the back store room. _____ Replace or repair the broken outlet (office #2)
12/11/2008 VIOL - FIRE PROTECTION SYSTEMS JLONGO Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. 906.6 Unobstructed and unobscured. Portable fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers. 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. ______ Service, tag, maintain, and properly hang all portable fire extinguishers according to code _____ Remove any items that may block access to the emergency portable fire extinguishers located in your back store room.
12/11/2008 VIOL - MEANS OF EGRESS JLONGO Correction Required 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1008.1.8.5 Unlatching. The unlatching of any door or leaf shall not require more than one operation. 1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of door leaf width. 2. The maximum unlatching force shall not exceed 15 pounds (67 N). 3. No additional locks or latches shall be added _____ Remove the drop bar system from the west rear egress door as well as removing all secondary locking devices; only an one opertaion system shall be approved. _____ Remove the drop bar system from your south egress door, leaving only an one opertaion system. 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists… -- 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: -- 2.1. The locking device is readily distinguishable as locked, -- 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, -- 2.3. The use of the key-operated locking device is revokable by the fire code official for due cause. _____ Place the wording "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" visibly above your main egress door. 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for the duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code _____ Fix, repair, and/or replace all exit signs in order to meet code standards
12/11/2008 VIOL - COMPRESSED GASES JLONGO Correction Required 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____ Properly secure all compressed gas cylinders at all times ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ____________________________ (Captain) Full inspection done by Inspector Joseph P. Longo Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: _____ ____________________ Passed on: ________ (Joseph P. Longo)