Case: T08FR04683
Case Details
Entered Date:
12/10/2008
Applicant:
CAMPBELL DAVID F TR
Description:
Full Fire Prevention Inspection.
Outstanding Inspections
Case Number: T08FR04683
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/10/2008 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 310.3- "NO SMOKING" signs. Post "NO SMOKING" signs on the east and west end of the shop. |
| 12/10/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6- Inspection, testing and maintenance. Service and tag all portable fire extinguishers. |
| 12/10/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8- Door operations. Remove the double keyed lock from the north door in the office. |
| 12/10/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8.3- Locks and latches. Post the wording "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED", on the inside of the entrance door located in the office. |
| 12/10/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1013.1- Where required. Guards shall be provided along the open side of the mezzanine located in the shop. |
| 12/10/2008 | VIOL - HAZARDOUS MATERIALS,GEN | JBURGE | Correction Required | TFC 2703.5.1- Markings. Post signs in the area of the antifreeze and used oil storage location. |
| 12/10/2008 | VIOL - HAZARDOUS MATERIALS,GEN | JBURGE | Correction Required | TFC 2703.8.7- Hazardous material storage cabinets. Reduce the quantity of flammable liquids or purchase an approved flammable liquids cabinet. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04683
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/10/2008 | INSP - FULL | JBURGE | Approved | Please correct all noted Tucson Fire Code violations. |