Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

12/01/2008

Applicant:

HENRY CMT DELB FLP

Description:

Santa Cruz veterinary full fire inspection

Outstanding Inspections

Case Number: T08FR04508
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
12/01/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
12/01/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Replace with approved power strip.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04508
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/01/2008 INSP - FULL JLOYA Approved Correct the following code violations found 11-28-08 during fire safety inspection.