Case: T08FR04504
Case Details
Entered Date:
12/01/2008
Applicant:
VALENCIA GATEWAY LLC 30.98% & SNYDER
Description:
Walgreen's full fire inspection
Outstanding Inspections
Case Number: T08FR04504
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/01/2008 | VIOL - PRECAUTION AGAINST FIRE | JLOYA | Violation | TFC 315.2.1 - Ceiling clearance. Storage shall be maintained 2 feet or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings. |
12/01/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer. |
12/01/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Replace with approved power strip. |
12/01/2008 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | TFC 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities. |
12/01/2008 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | TFC 901.6.2 - Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request. ___Provide records of last sprinkler system inspection. |
12/01/2008 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | TFC 906.6 - Unobstructed and unobscured. Portable fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers. |
12/01/2008 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04504
Case Description: INSPECTION
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/01/2008 | INSP - FULL | JLOYA | Approved | Correct the following code violations found 11-28-08 |
01/12/2009 | INSP - REINSPECTION | JLOYA | Approved | All violations abated. |