Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

11/26/2008

Applicant:

EL GANADO LTD PARTNERSHIP

Description:

Jack furrier full fire inspection

Outstanding Inspections

Case Number: T08FR04461
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
11/26/2008 VIOL - ADMINISTRATION JLOYA Violation 105.1 General. Permits shall be in accordance with Sections 105.1.1 through 105.7.13. ___ Provide tanks permits upon reinspection.
11/26/2008 VIOL - PRECAUTION AGAINST FIRE JLOYA Violation 309.4 Fire extinguishers. Battery-charging areas shall be provided with a fire extinguisher complying with Section 906 having a minimum 4-A:20-B:C rating within 20 feet (6096 mm) of the battery charger
11/26/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Replace with approved power strip.
11/26/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04461
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
11/26/2008 INSP - FULL JLOYA Approved Correct the folowing code violations found 11-26-08.
01/12/2009 INSP - REINSPECTION JLOYA Approved All violations abated.