Description:

Payless shoe source full fire inspection.

Outstanding Inspections

Case Number: T08FR04421
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
11/24/2008 VIOL - PRECAUTION AGAINST FIRE JLOYA Violation TFC 315.2.1 - Ceiling clearance. Storage shall be maintained 2 feet or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings.
11/24/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer.
11/24/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Replace with approved power strip.
11/24/2008 VIOL - FIRE RESIST.RATED CONST JLOYA Violation TFC 703.1 - The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. ***Replace missing ceiling tiles.
11/25/2008 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. __Fire extinguishers shall be mounted, unobscured, unobstructed and currently inspected.
11/25/2008 VIOL - MEANS OF EGRESS JLOYA Violation TFC 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit signs

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04421
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
11/24/2008 INSP - FULL JLOYA Approved Please correct the following deficiencies.
01/12/2009 INSP - REINSPECTION JLOYA Approved All violations abated.