Case: T08FR04413
Case Details
Entered Date:
11/24/2008
Applicant:
TUCSON MOB PARTNERS LTD
Description:
FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T08FR04413
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| VIOL - FIRE SERVICE FEATURES | None | Not Inspected | ||
| 11/24/2008 | VIOL - BUILDING SVCS & SYSTEMS | MWAINWRI | Violation | 2006 IFC 605.1 REMOVE TABLE IN FRONT OF ELECTRICAL RM PEDS |
| 11/24/2008 | VIOL - BUILDING SVCS & SYSTEMS | MWAINWRI | Violation | 2006 IFC 605.5 REMOVE EXTENSION CORD IN SOUTH SIDE EMS USED AS PERMENACNT WIRING FOR COMPUTERS |
| 11/24/2008 | VIOL - FIRE PROTECTION SYSTEMS | MWAINWRI | Violation | 2006 IFC 901.6 SPRINKLER HEAD NEEDS ESCHEON IN TRACER ROOM AZ ORTHO ACROSS FROM EXAM RM 4 NEEDS AN ESCHEON PEDS BREAK RM NEED 3 ESCHEONS |
| 11/24/2008 | VIOL - FIRE PROTECTION SYSTEMS | MWAINWRI | Violation | 2006 IFC 901.6 SQL 2ND FLOOR STORAGE ROOM SPRINKLER HEAD NEEDS TO BE ADJUSTED FOR THE HEAD TO BE EFFECTIVE. |
| 11/24/2008 | VIOL - MEANS OF EGRESS | MWAINWRI | Violation | 2006 IFC 1027.3 REPAIR EXIT SIGNS THROUGH OUT THE BUILDING. |
| 11/24/2008 | VIOL - MEANS OF EGRESS | MWAINWRI | Violation | 2006 IFC 1027.5 REPAIR ALL EMERGENCY LIGHTS SO THEY OPERATE IN BATTERY BACKUP |
| 11/24/2008 | VIOL - MEANS OF EGRESS | MWAINWRI | Violation | 2006 IFC 1027.5 REPAIR EMERGENCY LIGHT IN TRACER ROOM AND ELEC ROOM 2013-2014 REPAIR EMERGENCY LIGHT IN STAIRWELL NORTH LL 03 |
| 11/24/2008 | VIOL - MEANS OF EGRESS | MWAINWRI | Violation | 206 IFC 1027.16.7 KEEP EMERGENCY ISLE OPEN IN TRANSCRIBING ROOM |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04413
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/11/2010 | INSP - FULL | MWAINWRI | Approved |