Applicant:
MAVERICK HOLDING COMPANY LLC 56% &
Description:
food city fire inspection 12th and valencia
Outstanding Inspections
Case Number: T08FR04407
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/21/2008 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Exception. **************************************************************************** Security bolt on rear door: To ensure that there is no confusion on the required exiting from the building the following must be completed: 1. A sign stating "NOT AN EXIT" affixed to the interior side of the door. The sign shall consist of letters having a principal stroke of not less than 0.75 inch wide and at least 6 inches high on a contrasting background. 2. A sign stating "THIS DOOR BLOCKED" affixed to the exterior side of the door. The sign shall consist of letters having a principal stroke of not less than 0.75 inch wide and at least 6 inches high on a contrasting background. |
11/21/2008 | VIOL - COMPRESSED GASES | JLOYA | Violation | 3003.5 Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgement and against access by unauthorized personnel in accordance with Sections 3003.5.1 through 3003.5.3. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04407
Case Description: INSPECTION
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/21/2008 | INSP - FULL | JLOYA | Approved | Full fire inspection done @food city store #165 |