Case: T08FR04377
Case Details
Entered Date:
11/20/2008
Applicant:
GREEN WAVE OF ARIZONA INC
Description:
PLS CHECK CASHING FULL INSPECTION TO BE RECOMMENDED FOR SELF INSPECTION.
Outstanding Inspections
Case Number: T08FR04377
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/20/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. ___Remove multi plug adapter on ceiling outlet by east wall. |
| 12/01/2008 | VIOL - MEANS OF EGRESS | JLOYA | Violation | TFC 1006.1 - Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____ Provide emergency lighting that is activated by loss of power to building. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04377
Case Description: INSPECTION
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/20/2008 | INSP - FULL | JLOYA | Approved | PLEASE CORRECT THE FOLLOWING DEFICIENCIES FOUND DURING FIRE/SAFETY INSPECTION CONDUCTED 11-19-08 |
| 12/01/2008 | INSP - REINSPECTION | JLOYA | Approved | All violations abated |