Description:

POLLO FELIZ FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T08FR04376
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
11/20/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Replace with approved power strip.
11/20/2008 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.11.6.3 - Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises.
11/20/2008 VIOL - MEANS OF EGRESS JLOYA Violation TFC 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit signs (BACK DOOR)
11/20/2008 VIOL - COMPRESSED GASES JLOYA Violation 3003.5 Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgement and against access by unauthorized

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04376
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
11/20/2008 INSP - FULL JLOYA Approved PLEASE CORRECT THE FOLLOWING CODE VIOLATIONS FOUND DURING THE FIRE INSPECTION CONDUCTED 11-19-08.
12/04/2008 INSP - REINSPECTION JLOYA Approved All violations abated.