Description:

YOKOHMA RICA BOWL FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T08FR04372
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
11/19/2008 VIOL - PRECAUTION AGAINST FIRE JLOYA Violation TFC 315.2.1 - Ceiling clearance. Storage shall be maintained 2 feet or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings.
11/19/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. (OFFICE)
11/19/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Replace with approved power strip (FRONT COUNTER PHONE).
11/19/2008 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.11.6.3 - Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises __ provide records of last cleanout of grease extractor ducts.
11/19/2008 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.11.6.5 Fusible link and sprinkler head replacement. Fusible links and automatic sprinkler heads shall be replaced at least annually, and other protection devices shall be serviced or replaced in accordance with the manufacturer's instructions. __ Replace nozzle caps over griddle
11/19/2008 VIOL - COMPRESSED GASES JLOYA Violation 3003.5 Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgement and against access by unauthorized personnel in accordance with Sections 3003.5.1 through 3003.5.3.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04372
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
11/19/2008 INSP - FULL JLOYA Approved FIRE SAFETY INSPECTION CONDUCTED 11-19-08 WITH THE FOLLOWING DEFICIENCIES FOUND.
02/04/2009 INSP - REINSPECTION JLOYA Approved All violations abated, hood extinguishing system found to be out of order by inspecting company. United fire stated they were taking care of issue but time was needed to get permits.