Case: T08FR04314
Case Details
Entered Date:
11/13/2008
Applicant:
WEINGARTEN NOSTAT INC
Description:
Full Fire Prevention Inspection.
Outstanding Inspections
Case Number: T08FR04314
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/13/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3-Working space and clearance. Remove storage located in front of the electrical service panel in the back room. |
11/13/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8.4- Bolt locks. Remove the surface bolt from the door in the back room. NOTE:Replace the surface bolt with a thumb-turn deadbolt. |
11/13/2008 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | TFC 3003.5.3- Securing Compressed gas containers, cylinders and tanks. Secure the CO2 cylinders located in the kitchen area with one or more restraints to prevent falling. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04314
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/28/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected. |