Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

11/13/2008

Applicant:

WEINGARTEN NOSTAT INC

Description:

Full Fire Prevention Inspection.

Outstanding Inspections

Case Number: T08FR04314
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
11/13/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3-Working space and clearance. Remove storage located in front of the electrical service panel in the back room.
11/13/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.4- Bolt locks. Remove the surface bolt from the door in the back room. NOTE:Replace the surface bolt with a thumb-turn deadbolt.
11/13/2008 VIOL - COMPRESSED GASES JBURGE Correction Required TFC 3003.5.3- Securing Compressed gas containers, cylinders and tanks. Secure the CO2 cylinders located in the kitchen area with one or more restraints to prevent falling.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04314
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/28/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected.