Case: T08FR04305
Case Details
Entered Date:
11/12/2008
Applicant:
PALERMO RICHARD & GLENDA TRUSTEES OF
Description:
System Hood Complaint
Outstanding Inspections
Case Number: T08FR04305
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/10/2009 | INSP - REINSPECTION | BCORRALE | Continued | RI on 02Jul, work is being bid on. Owner wil call to advise who will do the work. |
| 07/10/2009 | VIOL - FIRE PROTECTION SYSTEMS | BCORRALE | Continued | Systems lack electrical shutoffs. 904.11.2 System interconnection. The actuation of the fire extinguishing system shall automatically shut down the fuel or electrical power supply to the cooking equipment. The fuel and electrical supply reset shall be manual. *** Install proper electrical resets. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04305
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/12/2008 | INSP - FULL | RESSLING | Approved | Per hood system report (attached to form in log book), there is no electric shut down. |