Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

11/12/2008

Applicant:

PALERMO RICHARD & GLENDA TRUSTEES OF

Description:

System Hood Complaint

Outstanding Inspections

Case Number: T08FR04305
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
07/10/2009 INSP - REINSPECTION BCORRALE Continued RI on 02Jul, work is being bid on. Owner wil call to advise who will do the work.
07/10/2009 VIOL - FIRE PROTECTION SYSTEMS BCORRALE Continued Systems lack electrical shutoffs. 904.11.2 System interconnection. The actuation of the fire extinguishing system shall automatically shut down the fuel or electrical power supply to the cooking equipment. The fuel and electrical supply reset shall be manual. *** Install proper electrical resets.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04305
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/12/2008 INSP - FULL RESSLING Approved Per hood system report (attached to form in log book), there is no electric shut down.