Case: T08FR04299
Case Details
Entered Date:
11/12/2008
Applicant:
HOGAN SCHOOL OF REAL ESTATE INC
Description:
SPRINKLER INSPECTION
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04299
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/12/2008 | INSP - FULL | EDESCHAI | Approved | DURING THE ANNUAL FIRE SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE. 1) THE WATER MOTOR GONG FAILED DURING THE FLOW TEST 2) THE FIRE SPRINKLER RISER IS DUE FOR THE 5 YEAR INTERNAL INSPECTION 3) AN EMERGENCY SPARE SPRINKLER BOX SHALL BE PROVIDED AT THE SPRINKLER RISER WITH THE CORRECT COMPLIMENT OF HEADS AND A SPECIAL WRENCH |