Case Details

Status:

COMPLETE

Type:

COMPLAINT (COMMERCIAL)

Entered Date:

11/12/2008

Applicant:

SULLIVAN THOMAS W

Description:

SPRINKLER INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04290
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/12/2008 INSP - FULL EDESCHAI Approved DURING THE ANNUAL SPRINKLER INSPECTION OF 11-10-2008, THE FOLLOWIND DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE 1) THE PRESSURE GUAGES WERE INOPERABLE TO CORRECTLY GET READINGS 2) THE WATER MOTOR GONG FAILED THE FLOW TEST 3) SPRINKLER RISER IS DUE FOR THE 5 YEAR INTERNAL INSPECTION