Case: T08FR04263
Case Details
Entered Date:
11/07/2008
Applicant:
GS PROPERTY INVESTMENTS LLC
Description:
BUZZ SPORTS HAIRCUTS FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T08FR04263
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/07/2008 | VIOL - PRECAUTION AGAINST FIRE | JLOYA | Violation | TFC 315.2.1 - Ceiling clearance. Storage shall be maintained 2 feet or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings. |
| 11/07/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. ___ RESOLVED |
| 11/07/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Replace with approved power strip. |
| 11/07/2008 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | TFC 906.7 - Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. |
| 11/13/2008 | INSP - REINSPECTION | JLOYA | Violation | REINSPECTION CONDUCTED 11/13/08 VIOLATIONS STILL UNRESOLVED. 2ND REINSPECTION DONE 11-18-08 WITHA LL VIOLATIONS ABATED. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04263
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/07/2008 | INSP - FULL | JLOYA | Approved | FULL FIRE INSPECTION FOR RECOMENDATION INTO SELF INSPECTION PROGRAM |