Case: T08FR04259
Case Details
Entered Date:
11/07/2008
Applicant:
MAVERICK HOLDING COMPANY LLC 56% &
Description:
AMERICAN FAMILY INS FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T08FR04259
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/07/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. ___ REPLACE JUNCTION BOX COVER |
11/07/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.4.2 - Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle. ___ CORRECTED |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04259
Case Description: INSPECTION
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/13/2008 | INSP - REINSPECTION | JLOYA | Approved | RINSPECTION DONE 11/13/08 WITH JNCTION COVERS STILL UNCOVERED TO BE REINSPECTED 11/14/08 |
11/18/2008 | INSP - FULL | JLOYA | Approved | FINALL REINSPECTION DONE 11-14-08 WITH ALL VIOLATIONS ABATED. BUSINESS TO BE RECOMENDED FOR SELF INSPECTION PROGRAM |