Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

11/06/2008

Applicant:

MAVERICK HOLDING COMPANY LLC 56% &

Description:

TNT FASHION FULL FIRE INSPECTION CONDUCTED 11-05-08

Outstanding Inspections

Case Number: T08FR04228
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
11/06/2008 VIOL - ADMINISTRATION JLOYA Violation Please provide a copy of your Certificate of Occupancy [C of O] upon re-inspection.
11/06/2008 VIOL - PRECAUTION AGAINST FIRE JLOYA Violation TFC 315.2.1 - Ceiling clearance. Storage shall be maintained 2 feet or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings.
11/06/2008 VIOL - PRECAUTION AGAINST FIRE JLOYA Violation TFC 315.2.2 - Means of egress. Combustible materials shall not be stored in exits or exit enclosures.
11/06/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Replace with approved power strip.
11/06/2008 VIOL - MEANS OF EGRESS JLOYA Violation TFC 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit signs

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04228
Case Description: INSPECTION
Total Completed Inspections - 3
End Date Description Inspector Results Comments
11/06/2008 INSP - FULL JLOYA Approved INSPECTION WAS DONE WITH OWNER PRESENT AT TIME OF REOPRT DELIVERY MR LEE HAD STEPPED OUT , REPORT HANDED TO ATTENDANT
11/06/2008 INSP - FULL JLOYA Approved FULL FIRE INSPECTION DONE 11-05-08
11/19/2008 INSP - REINSPECTION JLOYA Approved REINSPECTION DONE 11-18-08 WITH ALL VIOLATIONS ABATED.