Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

11/05/2008

Applicant:

MC DONALD S CORPORATION

Description:

McDONALD'S FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T08FR04180
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
11/05/2008 VIOL - FIRE SERVICE FEATURES JLOYA Violation 505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. Address numbers shall be in accordance with Pima County address display requirements.
11/05/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.3.1 Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording. The disconnecting means for each service, feeder or branch circuit originating on a switchboard or panelboard shall be legibly and durably marked to indicate its purpose unless such purpose is clearly evident. ***Provide such signage.
11/05/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Replace with approved power strip.
11/05/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes
11/05/2008 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.11.6 Operations and maintenance. Commercial cooking systems shall be operated and maintained in accordance with this section. ____REPLACE NOZZLE COVERS
11/05/2008 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation TFC 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.
11/05/2008 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation TFC 906.5 - Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel.
11/05/2008 VIOL - MEANS OF EGRESS JLOYA Violation 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 1. Places of detention or restraint. 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: 2.1. The locking device is readily distinguishable as locked, 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch high on a contrasting background, 2.3. The use of the key-operated locking device is revokable by the fire code official for due cause.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04180
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
11/05/2008 INSP - FULL JLOYA Approved FULL FIRE INSPECTION CONDUCTED 11-04-08 PROPERTY REP WAS MARY LEVINSKIB
11/28/2008 INSP - REINSPECTION JLOYA Approved All violations abated noted on final inspection11-28-08.