Case: T08FR04160
Case Details
Entered Date:
11/04/2008
Applicant:
MAVERICK HOLDING COMPANY LLC 56% &
Description:
99 CENT DISCOUNT STORE FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T08FR04160
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/04/2008 | VIOL - ADMINISTRATION | JLOYA | Violation | C of O to be provided upon re-inspection, if available. If not available, manager will be in the process of acquiring it. |
11/04/2008 | VIOL - PRECAUTION AGAINST FIRE | JLOYA | Violation | TFC 315.2.1 - Ceiling clearance. Storage shall be maintained 2 feet or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings |
11/04/2008 | VIOL - FIRE SERVICE FEATURES | JLOYA | Violation | 505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. Address numbers shall be in accordance with Pima County address display requirements. |
11/04/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.3.1 Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording. The disconnecting means for each service, feeder or branch circuit originating on a switchboard or panelboard shall be legibly and durably marked to indicate its purpose unless such purpose is clearly evident |
11/04/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Replace with approved power strip. |
11/04/2008 | VIOL - FIRE RESIST.RATED CONST | JLOYA | Violation | TFC 703.3 - The hanging and displaying of salable goods and other decorative materials from acoustical ceiling systems that are part of a fire-resistance-rated floor/ceiling or roof/ceiling assembly, shall be prohibited. ***Remove ceiling decorations |
11/04/2008 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. |
11/04/2008 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use, including the accumulation of snow and ice. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04160
Case Description: INSPECTION
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/04/2008 | INSP - FULL | JLOYA | Approved | FULL FIRE INSPECTION DONE 11-3-08 |
11/18/2008 | INSP - REINSPECTION | JLOYA | Approved | REINSPECTIONS FINISHED 11-18-08 WITH ALL VIOLATIONS FOUND ABATED |