Case: T08FR04152
Case Details
Entered Date:
11/03/2008
Applicant:
STONE AVENUE STANDARD LLC
Description:
SPRINKLER INSPECTION
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04152
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/03/2008 | INSP - FULL | EDESCHAI | Approved | DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. ACOPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE 1) BUILDING # 1-NORTH A) SPRINKLER RISER IS DUE FOR 5 YEAR INTERNAL INSP. B) SPARE HEAD BOX NEEDS 3 UPRIGHT SPRINKLERS 2) BUILDING # 2 SOUTH A) RISER DUE FOR 5 YEAR INTERNAL INSPECTION B) PROVIDE FIRE DEPT. CONNECTION CAPS C) SPARE HEAD BOX NEEDS 3 UPRIGHT SPRINKLERS D) LOWER SPRINKLER IN RISER ROOM FOR CORRECT COVERAGE |