Case: T08FR04130
Case Details
Entered Date:
11/03/2008
Applicant:
CHAVEZ MANUEL NABOR & LUZ MARINA CP/RS
Description:
UNITED AUTO REPAIR FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T08FR04130
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/03/2008 | VIOL - PRECAUTION AGAINST FIRE | JLOYA | Violation | 309.4 Fire extinguishers. Battery-charging areas shall be provided with a fire extinguisher complying with Section 906 having a minimum 4-A:20-B:C rating within 20 feet (6096 mm) of the battery charger. |
| 11/03/2008 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. |
| 11/03/2008 | VIOL - TENTS, CANOPIES & OTHER | JLOYA | Violation | 2403.2 Approval required. Tents and membrane structures having an area in excess of 400 square feet (37m2) and canopies in excess of 900 square feet (84m2) shall not be erected, operated or maintained for any purpose without first obtaining a permit and approval from the fire code official. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04130
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/18/2008 | INSP - FULL | JLOYA | Approved | REINSPECTION DONE 11-14-08 ALL CODE VOILATIONS ABATED |