Description:

UNITED AUTO REPAIR FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T08FR04130
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
11/03/2008 VIOL - PRECAUTION AGAINST FIRE JLOYA Violation 309.4 Fire extinguishers. Battery-charging areas shall be provided with a fire extinguisher complying with Section 906 having a minimum 4-A:20-B:C rating within 20 feet (6096 mm) of the battery charger.
11/03/2008 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
11/03/2008 VIOL - TENTS, CANOPIES & OTHER JLOYA Violation 2403.2 Approval required. Tents and membrane structures having an area in excess of 400 square feet (37m2) and canopies in excess of 900 square feet (84m2) shall not be erected, operated or maintained for any purpose without first obtaining a permit and approval from the fire code official.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04130
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/18/2008 INSP - FULL JLOYA Approved REINSPECTION DONE 11-14-08 ALL CODE VOILATIONS ABATED