Case: T08FR04125
Case Details
Entered Date:
11/03/2008
Applicant:
FAMILY DOLLAR INC
Description:
FAMILY DOLLAR FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T08FR04125
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/03/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer. |
11/03/2008 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. |
11/03/2008 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1008.1.8.3 Locks and latches 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch high on a contrasting background, |
11/03/2008 | VIOL - MEANS OF EGRESS | JLOYA | Violation | TFC 1006.1 - Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04125
Case Description: INSPECTION
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/03/2008 | INSP - FULL | JLOYA | Approved | FULL FIRE INSPECTION DONE 10-31-08 |
11/21/2008 | INSP - REINSPECTION | JLOYA | Approved | All violations abated. |