Description:

SPRINKLER INSPECTION

Completed Inspections

Case Status: FIELD
Case Number: T08FR04121
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/03/2008 INSP - FULL EDESCHAI Approved DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE. 1) THE SPRINKLER RISER IS DUE FOR THE 5 YEAR INTERNSL INSPECTION 2) THE EMERGENCY HEAD BOX REQUIRES THE INSTALLATION OF ONE CHROME PENDANT 3) THE SUPPLY GUAGE IS IN NEED OF REPAIR OR REPLACEMENT