Case: T08FR04082
Case Details
Entered Date:
10/31/2008
Applicant:
GONZALEZ HECTOR
Description:
THE TACO SHOP FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T08FR04082
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/31/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. ___ REPLACE ALL OUTLET AND JUNCTION BOXES COVERS. |
| 10/31/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer. |
| 10/31/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Replace with approved power strip. |
| 10/31/2008 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 904.5 Wet-chemical systems. Wet-chemical extinguishing systems shall be installed, maintained, periodically inspected and tested in accordance with NFPA 17A and their listing. |
| 10/31/2008 | VIOL - COMPRESSED GASES | JLOYA | Violation | TFC 3003.3 Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgment and against access by unauthorized personnel in accordance with Sections 3003.3.1 through 3003.3.3. *** Secure gas cylinder to avoid accidental dislodgment, in an approved manner. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04082
Case Description: INSPECTION
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/31/2008 | INSP - FULL | JLOYA | Approved | FULL FIRE INSPECTION DONE 10-30-08 |
| 11/20/2008 | INSP - REINSPECTION | JLOYA | Approved | 2nd reinspection conducted 11-20-08 with all violations resolved |