Description:

THE TACO SHOP FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T08FR04082
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
10/31/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. ___ REPLACE ALL OUTLET AND JUNCTION BOXES COVERS.
10/31/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer.
10/31/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Replace with approved power strip.
10/31/2008 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.5 Wet-chemical systems. Wet-chemical extinguishing systems shall be installed, maintained, periodically inspected and tested in accordance with NFPA 17A and their listing.
10/31/2008 VIOL - COMPRESSED GASES JLOYA Violation TFC 3003.3 Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgment and against access by unauthorized personnel in accordance with Sections 3003.3.1 through 3003.3.3. *** Secure gas cylinder to avoid accidental dislodgment, in an approved manner.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04082
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
10/31/2008 INSP - FULL JLOYA Approved FULL FIRE INSPECTION DONE 10-30-08
11/20/2008 INSP - REINSPECTION JLOYA Approved 2nd reinspection conducted 11-20-08 with all violations resolved