Case: T08FR04081
Case Details
Entered Date:
10/31/2008
Applicant:
FAYWEST ENTERPRISES
Description:
AAMCO FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T08FR04081
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/31/2008 | VIOL - ADMINISTRATION | JLOYA | Violation | 105.1 General. Permits shall be in accordance with Sections 105.1.1 through 105.7.13. ___ PERMITS PRESENT IN PREMISES |
| 10/31/2008 | VIOL - PRECAUTION AGAINST FIRE | JLOYA | Violation | 310.1 General. The smoking or carrying of a lighted pipe, cigar, cigarette or any other type of smoking paraphernalia or material is prohibited in the areas indicated in this section. ___ SMOKING NOT SEEN DURING REINSPECTION |
| 10/31/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. |
| 10/31/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer. |
| 10/31/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. __ REPLACE WIRE CAGE AROUND SPRINKLERS. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04081
Case Description: INSPECTION
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/31/2008 | INSP - FULL | JLOYA | Approved | FULL FIRE INSPECTION CONDUCTED 10-30-08 |
| 11/13/2008 | INSP - REINSPECTION | JLOYA | Approved | REINSPECTION CONDUCTED WITH VIOLATIONS STILL PRESENT 2ND REINSPECTION TO BE DONE 11/20/08 All violationsw abated 11-24-08 |