Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

10/30/2008

Applicant:

ASH PAUL 80% & BJA INVESTMENT LTD

Description:

BRAKE MASTERS FIRE INSPECTON

Outstanding Inspections

Case Number: T08FR04067
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
10/30/2008 VIOL - ADMINISTRATION JLOYA Violation 105.1 General. Permits shall be in accordance with Sections 105.1.1 through 105.7.13. __ PROVIDE PERMITS FOR OIL TANKS.
10/30/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer.
10/30/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Replace with approved power strip.
10/30/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
10/30/2008 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation TFC 906.6 - Unobstructed and unobscured. Portable fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04067
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
10/30/2008 INSP - FULL JLOYA Approved FULL FIRE INSPECTION DONE
11/13/2008 INSP - REINSPECTION JLOYA Approved ALL VIOLATIONS CORRECTED