Case: T08FR04067
Case Details
Entered Date:
10/30/2008
Applicant:
ASH PAUL 80% & BJA INVESTMENT LTD
Description:
BRAKE MASTERS FIRE INSPECTON
Outstanding Inspections
Case Number: T08FR04067
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/30/2008 | VIOL - ADMINISTRATION | JLOYA | Violation | 105.1 General. Permits shall be in accordance with Sections 105.1.1 through 105.7.13. __ PROVIDE PERMITS FOR OIL TANKS. |
| 10/30/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer. |
| 10/30/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Replace with approved power strip. |
| 10/30/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. |
| 10/30/2008 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | TFC 906.6 - Unobstructed and unobscured. Portable fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04067
Case Description: INSPECTION
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/30/2008 | INSP - FULL | JLOYA | Approved | FULL FIRE INSPECTION DONE |
| 11/13/2008 | INSP - REINSPECTION | JLOYA | Approved | ALL VIOLATIONS CORRECTED |