Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

10/30/2008

Applicant:

WONG JAMES Y & WONG ANNA L

Description:

GRAND MARKET FULL INSPECTION

Outstanding Inspections

Case Number: T08FR04061
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
10/30/2008 VIOL - PRECAUTION AGAINST FIRE JLOYA Violation 315.2 Storage in buildings. Storage of combustible materials in buildings shall be orderly. Storage shall be separated from heaters or heating devices by distance or shielding so that ignition cannot occur.
10/30/2008 VIOL - PRECAUTION AGAINST FIRE JLOYA Violation TFC 315.2.1 - Ceiling clearance. Storage shall be maintained 2 feet or more below the ceiling in nonsprinklered areas of buildings
10/30/2008 VIOL - FIRE SERVICE FEATURES JLOYA Violation TFC 505.1 - Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. Address numbers shall be in accordance with Pima County address display requirements. ***1. Address shall be displayed in an approved manner. Manager received a copy of the "Pima County Address Display Requirements" flyer.
10/30/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.3.1 Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording. The disconnecting means for each service, feeder or branch circuit originating on a switchboard or panelboard shall be legibly and durably marked to indicate its purpose unless such purpose is clearly evident. ***Provide such signage.
10/30/2008 VIOL - MEANS OF EGRESS JLOYA Violation TFC 1014.4.1 - Aisles in Groups B and M. In Group B and M occupancies, the minimum clear aisle width shall be determined by Section 1005.1 for the occupant load served, but shall not be less than 36 inches
11/13/2008 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04061
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/13/2008 INSP - REINSPECTION JLOYA Approved REINSPECTION CONDUCTED WITH ALL VIOLATIONS ABATED