Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T08FR03937
Case Details
Entered Date:
10/24/2008
Applicant:
BM VALENCIA LLC
Description:
EEGEE'S FIRE INSPECTION
Outstanding Inspections
Case Number: T08FR03937
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/24/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. __ SPACE CLEARED ____ Clear area around electrical panels. |
10/24/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.4.1 - Power tap design. Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed in accordance with UL 1363. |
11/13/2008 | INSP - REINSPECTION | JLOYA | Violation | REINSPECTION CONDUCTED 11/13/08 ANOTHER REINSPECTION TO TAKE PLACE 11/17/08 ALL VIOLATIONS ABATED 11-18-08 |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR03937
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/24/2008 | INSP - FULL | JLOYA | Approved | FULL INSPECTION DONE ON 10/24/05 |