Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

10/24/2008

Applicant:

BM VALENCIA LLC

Description:

EEGEE'S FIRE INSPECTION

Outstanding Inspections

Case Number: T08FR03937
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
10/24/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. __ SPACE CLEARED ____ Clear area around electrical panels.
10/24/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.4.1 - Power tap design. Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed in accordance with UL 1363.
11/13/2008 INSP - REINSPECTION JLOYA Violation REINSPECTION CONDUCTED 11/13/08 ANOTHER REINSPECTION TO TAKE PLACE 11/17/08 ALL VIOLATIONS ABATED 11-18-08

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR03937
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/24/2008 INSP - FULL JLOYA Approved FULL INSPECTION DONE ON 10/24/05